Data whose decimal point's presence and/or position depends on input range.
Example:When Read messured value(PV) is -20.0°c,-20.0 is processed as -200;
When Read PID output value is 20,20 is processed as 20 too,bceause PID output value have no decimal point ;
Universal register address: | ||||
---|---|---|---|---|
ID | NAME | Decimal point | Real Register | Holding Register |
0 | Messured value(PV): | yes | 1001H | 44098 |
1 | Manipulated output value (MV): | no | 1101H | 44354 |
2 | Alarm output: | no | 1200H | 44609 |
KCM-8 Digital Level Indicator | ||||
---|---|---|---|---|
ID | NAME | Decimal point | Real Register | Holding Register |
0 | Alarm1 value | 1 | 0000H | 40001 |
1 | Alarm2 Differential gap | 1 | 0001H | 40002 |
2 | Alarm2 value | 1 | 0002H | 40003 |
3 | Alarm2 Differential gap | 1 | 0003H | 40004 |
4 | Alarm3 value | 1 | 0004H | 40005 |
5 | Alarm3 Differential gap | 1 | 0005H | 40006 |
6 | Alarm4 value | 1 | 0006H | 40007 |
7 | Alarm4 Differential gap | 1 | 0007H | 40008 |
8 | Set data lock | 0 | 0008H | 40009 |
9 | PV Bias | 0 | 0009H | 40010 |
10 | Decimal position | 0 | 000AH | 40011 |
11 | Range high | 1 | 000BH | 40012 |
12 | Range low | 1 | 000CH | 40013 |
13 | beams high | 1 | 000DH | 40014 |
14 | beams low | 1 | 000EH | 40015 |
15 | Digital Filter | 0 | 000FH | 40016 |
16 | Alarm type | 0 | 0010H | 40017 |
17 | Alarm type | 0 | 0011H | 40018 |
18 | Alarm type | 0 | 0012H | 40019 |
19 | Alarm type | 0 | 0013H | 40020 |
KCM-7(Analog Current/Voltage input tempterature Controller) | ||||
---|---|---|---|---|
ID | NAME | Decimal point | Real Register | Holding Register |
0 | Setting Value | 1 | 0000 | 40001 |
1 | Alarm value | 1 | 0001 | 40002 |
2 | ALM Differential gap | 1 | 0002 | 40003 |
3 | PV Bias | 1 | 0003 | 40004 |
4 | Differential gap | 1 | 0004 | 40005 |
5 | Proportional band | 1 | 0005 | 40006 |
6 | Integral time | 0 | 0006 | 40007 |
7 | Derivative time | 0 | 0007 | 40008 |
8 | Control response time | 0 | 0008 | 40009 |
9 | Auto tuning | 0 | 0009 | 40010 |
10 | System function Opt. | 0 | 000A | 40011 |
11 | Alarm type | 0 | 000B | 40012 |
12 | Digital Filter | 0 | 000C | 40013 |
13 | Range high | 1 | 000D | 40014 |
14 | Range low | 1 | 000E | 40015 |
15 | Decimal position | 0 | 000F | 40016 |
16 | Set data lock | 0 | 0010 | 40017 |
17 | Initial U0 | 0 | 0011 | 40018 |
20 | Output limiter high | 0 | 0014 | 40021 |
21 | Output limiter low | 0 | 0015 | 40022 |