Data whose decimal point's presence and/or position depends on input range.
Example:When Read messured value(PV) is -20.0°c,-20.0 is processed as -200;
When Read PID output value is 20,20 is processed as 20 too,bceause PID output value have no decimal point ;
| Universal register address: | ||||
|---|---|---|---|---|
| ID | NAME | Decimal point | Real Register | Holding Register |
| 0 | Messured value(PV): | yes | 1001H | 44098 |
| 1 | Manipulated output value (MV): | no | 1101H | 44354 |
| 2 | Alarm output: | no | 1200H | 44609 |
| KCM-9(Thermocouple/RTD Universal input Temperature Controller) | ||||
|---|---|---|---|---|
| ID | NAME | Decimal point | Real Register | Holding Register |
| 0 | Setting Value | 1 | 0000H | 40001 |
| 1 | Alarm 1 value | 1 | 0001H | 40002 |
| 2 | Alarm 2 value | 1 | 0002H | 40003 |
| 3 | PV Bias | 1 | 0003H | 40004 |
| 4 | Proportional band | 0 | 0004H | 40005 |
| 5 | Integral time | 0 | 0005H | 40006 |
| 6 | Derivative time | 0 | 0006H | 40007 |
| 7 | Control response time | 0 | 0007H | 40008 |
| 8 | Digital Filter | 0 | 0008H | 40009 |
| 9 | Differential gap | 1 | 0009H | 40010 |
| 10 | Decimal position | 0 | 000AH | 40011 |
| 11 | Output limiter high | 0 | 000BH | 40012 |
| 12 | Output limiter low | 0 | 000CH | 40013 |
| 13 | Auto tuning | 0 | 000DH | 40014 |
| 14 | Set data lock | 0 | 000EH | 40015 |
| 15 | Input type | 0 | 000FH | 40016 |
| 16 | Control output | 0 | 0010H | 40017 |
| 18 | Alarm type | 0 | 0012H | 40019 |
| 19 | System function Opt. | 0 | 0013H | 40020 |
| 20 | Range high | 1 | 0014H | 40021 |
| 21 | Range low | 1 | 0015H | 40022 |
| KCM-9P(Ramp/soak Temperature controller) | ||||
|---|---|---|---|---|
| ID | NAME | Decimal point | Real Register | Holding Register |
| 0 | Setting Value | 1 | 0000H | 40001 |
| 1 | Alarm 1 value | 1 | 0001H | 40002 |
| 2 | Alarm 2 value | 1 | 0002H | 40003 |
| 3 | PV Bias | 1 | 0003H | 40004 |
| 4 | Proportional band | 0 | 0004H | 40005 |
| 5 | Integral time | 0 | 0005H | 40006 |
| 6 | Derivative time | 0 | 0006H | 40007 |
| 7 | Control response time | 0 | 0007H | 40008 |
| 8 | Digital Filter | 0 | 0008H | 40009 |
| 9 | Differential gap | 1 | 0009H | 40010 |
| 10 | Decimal position | 0 | 000AH | 40011 |
| 11 | Output limiter high | 0 | 000BH | 40012 |
| 12 | Output limiter low | 0 | 000CH | 40013 |
| 13 | Auto tuning | 0 | 000DH | 40014 |
| 14 | Set data lock | 0 | 000EH | 40015 |
| 15 | Input type | 0 | 000FH | 40016 |
| 16 | Control output | 0 | 0010H | 40017 |
| 18 | Alarm type | 0 | 0012H | 40019 |
| 19 | System function Opt. | 0 | 0013H | 40020 |
| 20 | Range high | 1 | 0014H | 40021 |
| 21 | Range low | 1 | 0015H | 40022 |
| 25 | Time Unit | 0 | 0019H | 40026 |
| 26 | Cycles | 0 | 001AH | 40027 |
| 27 | Power failure | 0 | 001BH | 40028 |
| 28 | Soak Band | 1 | 001CH | 40029 |
| 29 | Program control mode setting | 0 | 001DH | 40030 |
| 30 | Program segmentation | 0 | 001EH | 40031 |
| 31 | Run time | 0 | 001FH | 40032 |
| 32 | Ramp Time 1 | 1 | 0020H | 40033 |
| 33 | Soak Time 1 | 0 | 0021H | 40034 |
| 34 | Segment 1 Set value | 1 | 0022H | 40035 |
| 35 | Ramp Time 2 | 1 | 0023H | 40036 |
| 36 | Soak Time 2 | 0 | 0024H | 40037 |
| 37 | Segment 2 Set value | 1 | 0025H | 40038 |
| 125 | Ramp Time 32 | 1 | 007DH | 40126 |
| 126 | Soak Time 32 | 0 | 007EH | 40127 |
| 127 | Segment 3 Set value | 1 | 007FH | 40128 |